LIMITS OF TRANSFORMER TEMP. RISE
ElecMania
2015. 1. 7. 10:50
LIMITS OF TRANSFORMER TEMP. RISE | |||||||
No. | Description | IEC60076-1, 2000 IEC60076-2, 1993 IEC60354, 1991 |
IEEE C57.91-1995 IEEE C57.12.00-2000 |
Conclusion | Remarks | ||
1 | Reference Temperature | -25℃ ∼ +40℃ | clause 1.2.1 of IEC60076-1 | -30℃∼ +40℃ | clause 4.1.2.1 of IEEE C57.12.00 clause 6.4 of IEEE C57.91 |
Design temp is 40℃ | |
2 | Temperature Rise at Top-Oil | 60K | clause 4.2 of IEC60076-2 | 65℃ | clause 9.2.1 Table 8 of IEEE C57.91 | Different | |
3 | Temperature Rise at Winding | 65K | For transformers identified as ON.. or OF.. clause 4.2 of IEC60076-2 |
65℃ | clause 5.11.1.1 of IEEE C57.12.00 | 65℃ rise @40℃ (But 70℃ rise @OD.. cooling as per IEC) |
|
70K | For transformers identified as OD.. clause 4.2 of IEC60076-2 |
||||||
4 | Winding Hot Spot Temperature | up to 110℃ | clause 2.6.1 of IEC60354 Reference value is 98℃. But transformer with thermally upgraded insulation, the normal life expectancy is based on Hot Spot Temperature 110℃. |
80℃ rise | clause 5.11.1.1 of IEEE C57.12.00 clause 9.2.1 Table 8 of IEEE C57.91 |
80℃ rise @40℃ | |
5 | Core, of electrical connections outside the windings or of structural parts in the tank | No numerical limit | clause 4.2 of IEC60076-2 | Not excess of the winding hottest-spot temp. rise | clause 5.11.1.3 of IEEE C57.12.00 | No limits |