Footcandle Recommendations by Guth[1].pdf
http://www.gsa.gov/portal/content/101308
Table 6-3 Interior Illumination Levels (Average)
Area | Nominal Illumination Level in Lumens/Square Meter (lux) |
---|---|
Office Space | |
Normal work station space, open or closed offices1 |
500 |
ADP Areas |
500 |
Conference Rooms |
300 |
Training Rooms |
500 |
Internal Corridors |
200 |
Auditoria |
150-200 |
Public Areas |
|
Entrance Lobbies, Atria |
200 |
Elevator Lobbies, Public Corridors |
200 |
Ped. Tunnels and Bridges |
200 |
Stairwells |
200 |
Support Spaces | |
Toilets |
200 |
Staff Locker Rooms |
200 |
Storage Rooms, Janitors’ Closets |
200 |
Electrical Rooms, Generator Rooms |
200 |
Mechanical Rooms |
200 |
Communications Rooms |
200 |
Maintenance Shops |
200 |
Loading Docks |
200 |
Trash Rooms |
200 |
Specialty Areas | |
Dining Areas |
150-200 |
Kitchens |
500 |
Outleased Space |
500 |
Physical Fitness Space |
500 |
Child Care Centers |
500 |
Structured Parking, General Space |
50 |
Structured Parking, Intersections |
100 |
Structured Parking, Entrances |
500 |
1 Level assumes a combination of task and ceiling lighting where systems furniture is used. (This may include a combination of direct/indirect fixtures at the ceiling for ambient lighting.) NOTE: To determine footcandles (fc), divide lux amount by 11. |
http://www.engineeringtoolbox.com/light-level-rooms-d_708.html
Illumenance is measured in foot candles (ftcd, fc, fcd) (or lux in the metric SI system). A foot candle is actually one lumen of light density per square foot, one lux is one lumen per square meter.
Common light levels outdoor at day and night can be found in the table below:
Condition | Illumination | |
(ftcd) | (lux) | |
Sunlight | 10,000 | 107,527 |
Full Daylight | 1,000 | 10,752 |
Overcast Day | 100 | 1,075 |
Very Dark Day | 10 | 107 |
Twilight | 1 | 10.8 |
Deep Twilight | .1 | 1.08 |
Full Moon | .01 | .108 |
Quarter Moon | .001 | .0108 |
Starlight | .0001 | .0011 |
Overcast Night | .00001 | .0001 |
The outdoor light level is approximately 10,000 lux on a clear day. In the building, in the area closest to windows, the light level may be reduced to approximately 1,000 lux. In the middle area its may be as low as 25 - 50 lux. Additional lighting equipment is often necessary to compensate the low levels.
Earlier it was common with light levels in the range 100 - 300 lux for normal activities. Today the light level is more common in the range 500 - 1000 lux - depending on activity. For precision and detailed works, the light level may even approach 1500 - 2000 lux.
The table below is a guidance for recommended light level in different work spaces:
Activity | Illumination (lux, lumen/m2) |
Public areas with dark surroundings | 20 - 50 |
Simple orientation for short visits | 50 - 100 |
Working areas where visual tasks are only occasionally performed | 100 - 150 |
Warehouses, Homes, Theaters, Archives | 150 |
Easy Office Work, Classes | 250 |
Normal Office Work, PC Work, Study Library, Groceries, Show Rooms, Laboratories | 500 |
Supermarkets, Mechanical Workshops, Office Landscapes | 750 |
Normal Drawing Work, Detailed Mechanical Workshops, Operation Theatres | 1,000 |
Detailed Drawing Work, Very Detailed Mechanical Works | 1500 - 2000 |
Performance of visual tasks of low contrast and very small size for prolonged periods of time | 2000 - 5000 |
Performance of very prolonged and exacting visual tasks | 5000 - 10000 |
Performance of very special visual tasks of extremely low contrast and small size | 10000 - 20000 |
Illumination can be calculated as
I = Ll Cu LLF / Al (1)
where
I = illumination (lux, lumen/m2)
Ll = lumens per lamp (lumen)
Cu = coefficient of utilization
LLF = light loss factor
Al = area per lamp (m2)
10 incandencent lamps of 500 W (10600 lumens per lamp) are used in an area of 50 m2. With Cu = 0.6 and LLF = 0.8 illumination can be calculated as
I = 10 (10600 lumens) (0.6) (0.8) / (50 m2)
= 1018 lux